Radiantec Home


Radiantec

Detailed Description of Components and Materials



sun
"A good solar collector... should last the life of the building."

The function of the solar collector is to allow solar energy to enter the collector, then to turn the solar energy into heat energy, then to trap the heat so that it cannot get out, and finally to transfer the heat to a liquid (a heat transfer fluid) so that we can take the heat out and put it to use. A good solar collector is similar in construction to a commercial storefront window, and should last the life of the building.

A solar collector recommended by Radiantec will be simple, durable and reasonable in cost. It will be highly efficient at low to moderate temperatures, but will lose efficiency at very high temperatures. It will be free to high tech gizmos which raise high temperature performance but lower low temperature performance. It will not cause high temperature problems that need expensive solutions. A solar collector that can go up to 400 degrees F is not really your friend.

The important components of a liquid type solar collector are:

  1. The cover sheet.
  2. Absorber plate
  3. Rubber gasket.
  4. Frame material
  5. Insulating material.

Recall that whenever solar energy comes in contact with a material, the energy is either, transmitted through the material, or reflected off of the material, or absorbed by the material.

When we select the cover material, we will be looking for a material which transmits the maximum amount of solar energy, so that the sun's energy can get into the solar collector, and yet does not transmit heat energy, so that the energy is trapped. The material of choice is glass. Glass transmits most of the energy, but unfortunately, ten percent is still reflected off of the surface and about five percent is absorbed.

The glass cover sheet should be "low iron". Iron is a contaminant of glass that absorbs solar energy and gives the glass a greenish tint. Low iron glass will be vodka white when viewed on edge.

The cover sheet should be "tempered glass". Tempering greatly strengthens glass and if it does break, it will break into small pieces instead of large dangerous shards. It is just too dangerous to work with untempered glass and usually not responsible to those underneath.

Here, we will be looking for a material which absorbs the maximum amount of solar energy and also is able to conduct and transfer the heat to a liquid so that the heat can be pumped out of the collector and then put to use. The material of choice will be a copper sheet with a black coating and with copper tubing attached.

We need to select the absorber coating material with care. Not only must the material do its job of absorbing the sun's energy well, but it must also last a long time without peeling or discoloring. Some coating materials have so called "low emissivity" properties. All warm materials emit energy in the form of low wavelength infared waves (like a woodstove or a red-hot stovetop element). If we can reduce this emissivity, less energy will be radiated towards the cover sheet where some of it will be lost to the outside air. The result is a solar collector that conserves energy better at very high temperatures, but the collector will also stagnate at higher temperatures.

A solar collector is said to be in stagnation when bright sunlight is upon it, but the heat is not being taken away for some reason (a rolling blackout perhaps). Solar collectors must be able to withstand their stagnation temperatures in direct sunlight without damage and the rest of the system must be designed such that stagnation causes no harm or safety problems. The system must not boil over and should not damage other materials when the power comes back on and very hot antifreeze is pumped through they system. The system should not steam trap, so that the system will not flow because steam within the panels is acting like a large air bubble.

For these reasons, a solar heating collector provided by Radiantec will have an absorber plate with a "moderately selective" coating (It will absorb radiant energy well, but emit it only moderately). This absorber coating material will last a very long time because it is ceramic rather than a high-tech, multi-metal, coating process. It will give some added performance at higher temperatures, but not so much that it will cause additional problems upon stagnation.

It is important to keep water out of the solar collector. Water within the collector will turn to vapor under high temperature and then condense upon the inside of the cover material, causing appearance problems and some performance compromise. The only way to remedy the situation is to remove the cover sheet and clean it. Water can also cause corrosion problems.

Accordingly, collectors provided by Radiantec will have high quality EPDM gaskets around the cover sheet and at any plumbing connection. Also, any cracks or seams in the collector will be sealed with silicone rubber sealant.

The framing material, (top, bottom, and sides of the solar collector) should be a higher quality aluminum extrusion. Any metal that comes in contact with it should be chosen with care. When one metal comes into contact with another in a moisture environment, the whole thing becomes a weak battery. The metal most resistant to corrosion eats away at the other. In order to prevent this corrosion, any metal that comes in contact with another metal in a moisture environment should be either exactly the same metal, or should be stainless steel. The framing material is mitered like a picture frame and fastened with stainless steel crews. The joints must be carefully sealed with silicone rubber. A back plate, made of exactly the same grade material, is attached with rivets.

Insulation must be provided at the sides of the collector and also at the bottom. The insulation material must be stable at solar collector stagnation temperatures and should contain no impurities which could vaporize at stagnation temperatures and condense upon the cover sheet (outgassing). Do not use compressed fiberglass as this material contains petrochemical impurities which will outgas. Solar collectors recommended by Radiantec will have insulation made of polyisocyanurate.


A closed system is one that is not open to the outside environment. The solar heating loop is a closed system. Any closed system needs to have certain components for proper operation. The purpose of the plumbing mechanical package is to provide these components in a form that is complete, preassembled, pretested, and in the proper order. If you make the Plumbing Mechanical Package yourself, select the components with care according to the following criteria. Most problems with heating systems in general, and with solar heating systems in particular are caused by improper components or by components installed in the wrong place. It will help if you can do the work in the shop under ideal conditions and test it. Then bring it to the site for quick trouble free installation. Starting from the left to right, in the direct of flow:

This valve is a way to get the heat transfer fluid (HTF) out of the system for flushing or draining the system. It can be hooked up to a garden hose or washing machine hose. The valve itself should be Teflon seated ball valve instead of a rubber stopper because some HTFs will react with rubber and make a leak that will be a nuisance to repair.

You can use this valve to isolate most components in the PMP for easier repair. This valve can also adjust the flow to the HTF if necessary.

This valve allows flow in the proper direction, but prevents flow in the opposite direction. Without this valve, the solar loop would flow in the opposite direction by gravity all night long because the cold fluid in the collectors will be colder and denser than the fluid in the building. This action would cause heat loss to the building and could damage the domestic hot water heat exchanger. On bitterly cold nights, the HTF could go below the freezing point of water and cause the heat exchanger to rupture.

Allows the system to be flushed and filled with HTF. It should have the same construction as the drain valve.

It is worthwhile to spend the extra money on a good air eliminator. It must be installed of a horizontal section of pipe and should be installed at a point in the system with the lowest pressure (just before the pump). Air is not good for heating systems. Air interferes with heat exchange and promotes corrosion. A large enough air bubble will slow or even stop the flow of the HTF. If a quality air eliminator is installed at the low pressure point of the system, it can remove dissolved air and can even eliminate trapped air bubbles in remote locations. Air will come out of solution under low pressure at the air eliminator (just before the pump). On the other side of the pump, the HTF will be under higher pressure and will be able to dissolve air. If any flow at all can be established past a trapped air bubble, the HTF will dissolve the air bubble and bring the dissolved air back to the air eliminator for removal.

The air eliminator will have a screw cap on the top that must be loosened in order to allow air to escape. The screw cap will likely arrive in a tightened down position to avoid loss during shipment, and the air eliminator will not work until it is loosened.

All fluids will tend to expand in size when heated and contract in size when cooled. This expansion and contraction can present problems in a heating system that is closed (shut off from the environment) and rigid. Expansion of the HTF could cause a rigid system to burst or even explode. Contraction can cause air to enter through the air eliminator.

The expansion tank is basically a rubber balloon within a steel tank. This rubber bladder should be made from a material such as butyl rubber that is compatible with the antifreeze in the HTF, or the service life will be shortened. An expansion tank with an intact bladder will make a ringing sound when tapped with a metal object like a screwdriver. If the bladder within the expansion tank ruptures, the expansion will no longer perform its function. The system could lose pressure, or the pressure in the system may become erratic, or the pressure relief valve might discharge.

The pressure gauge will indicate the pressure within the system in pounds per square inch, at the location of the gauge. The system should have enough pressure in it to raise a column of water to the highest point in the system. Divide the vertical distance from the gauge to the highest point in the system by 2.3 to calculate the pressure required and then add 5 psi. In other words, if the vertical distance from the gauge to the top of the system is 16 ft., you should have 12 psi in the system. (16/2.3 = 6.9 psi + 5 psi = 12 psi)

Small variations in pressure (2 or 3 psi) are to be expected and are most likely due to daily temperature changes in the HTF, but other changes in pressure may indicate a problem.

If the pressure goes very high when the sun is out, the system may be flowing too slowly or not at all. Collector temperatures that are too high is confirmation.

If the system loses a little pressure every day, you probably have a leak somewhere.

If the system drops a few pounds but stabilizes at a lower pressure, the air eliminator has probably removed an air bubble.

If the system pressure falls to zero at night, but runs high during the day, the system has either lost HTF, or the expansion tank has failed, or both.

IF THE HEATING SYSTEM PRESSURE IS THE SAME AS THE BUILDING'S WATER PRESSURE, SUSPECT A BREACH IN THE WALL OF THE DOMESTIC HOT WATER HEAT EXCHANGER. ALSO SUSPECT CONTAMINATION OF THE POTABLE HOT WATER. DO NOT DRINK IT OR OTHERWISE USE IT UNTIL YOU ARE SURE THAT IT IS SAFE. THE PRESSURE RELEIF VALVE SHOULD BE SET LOWER THAN THE BUILDING'S WATER PRESSURE SO THAT THIS CONTAMINATION CANNOT OCCUR.

The pump needs to be carefully chosen for a) high quality material, and b) compatibility of the metals with the other metals in the system, and c) the ability of the pump to lift a column of HTF to the high point in the system (called pump head), and d) the ability of the pump to make the HTF flow at the proper rate, and e) the ability of the pump to do its work efficiently and with a minimum of electrical consumption.

Readers who have some familiarity with conventional heating systems know that boilers that are supplied today usually come with a pump, typically a small cheap one. I do not see how a pump can be selected without knowing anything about what kind of system the pump is going into or what the pump is going to have to do. This kind of sloppiness should not have become standard in the design of conventional heating systems, but there is no hope of a solar heating system working properly unless careful selection is paid to the pump.

If there is one thing to leave to an expert, pump selection might be it, but with the following material and the pump calculation procedures in the appendix, it can be done well. With the following information, the customer can at least verify that all important factors have been considered.

The pump is the only moving part in a Radiantec type solar heating system and this is not the place to pinch a penney. It is a reasonable goal to have a solar heating system to work flawlessly for 20 years or more. Then, replace the pump and the HTF, and have it work flawlessly for another 20 years or more. This is less maintenance than any heating system that I know of.

All moving parts should be stainless steel, but the shaft can be ceramic. If possible, the housing should be either bronze or stainless steel.

It is desirable, but not absolutely necessary, if the pump can lift a column of HTF to the high point in the system all by itself without help. When the system is properly full of fluid, the pump doesn't really have to do this. There is an equal column of HTF pulling downward to match the column of fluid going up, and the pump only has to circulate the fluid.

But if the system develops a large air bubble, or if it is trapped by steam, a smaller pump will not be able to move the fluid and a maintenance call will be needed to flush the system (but a steam trap will resolve itself when the sun goes down).

If the pump is big enough, however, all the homeowner need to do is add a little water with a garden hose, a procedure that takes ten minutes and requires no tools.

I should mention here that with reasonable workmanship and appropriate design, these problems will not happen in the first place.

A solar system should flow at the proper rate for best performance. There is some latitude here and flow does not have to be perfect for good operation, but proper flow can easily make a difference of 15-20% improvement in system energy harvest, and many owners of a solar heating system would never know the difference.

So that you will know the difference, here are the issues.

There are two types of flow. One is laminar flow, where the flow is fairly slow and smooth. Because of friction of the tubing wall, most of the flow goes through the center of the tube and the fluid nearest the wall does not circulate as well as it might. The other type of flow is turbulent flow, where the fluid sloshes around more because of its increased velocity.

Turbulent flow is good for heat exchange between the tubing and the HTF. Laminar flow is efficient as far as pump work is concerned.

What we want, is for the solar collectors and any heat exchangers to be in slightly turbulent flow. Too much turbulence wastes pump energy and in extreme cases can wear away the tubing material prematurely (erosion corrosion).

The tubing that connects the solar panels to the heat exchanger might as well be in laminar flow in order to save energy and achieve maximum service life. Use ¾" tubing up to 8 gallons per minute. Use 1" tubing up to 16 gallons per minute. Use 1 ¼" tubing up to 26 gallons per minute.

In general, a 4' X 8' solar collector should flow at the rate of 1-1 ½ gallons per minute. The temperature of the HTF coming out of the collector will be 10-15 degrees warmer than it went in under strong sunlight conditions.

This shut off valve can be used to isolate nearly all mechanical components between two valves for easier maintenance. It can also be used to adjust (meter) the flow.

This is the last line of defense against damage to the heating system from excessive pressure. The first line of defense is good design and the expansion tank. The pressure relief valve will vent the system to the atmosphere whenever a set pressure is exceeded. This valve should be set above any normal pressure situation that may occur, including stagnation. This is an emergency valve that is not designed to operate frequently. If it operates frequently because of some design flaw in the system, it will eventually start to leak and will need replacement. However, this valve should be tested once in a while to be sure that it still works and is not compromised by corrosion.

If this valve discharges, it could be quite hot, and it should be plumbed so that it will discharge in a safe place.

THIS VALVE MUST NEVER BE ISOLATED FROM THE HEAT PRODUCING EQUIPMENT (THE SOLAR COLLECTORS). THERE MUST BE NO SHUT OFF VALVE OR COMBINATION OF SHUT OFF VALVES THAT WOULD ISOLATE THE COLLECTORS FROM THE PRESSURE RELIEF VALVE.

SERIOUS MECHANICAL DAMAGE AND POTENTIAL FOR SERIOUS PERSONAL INJURY OR DEATH CAN RESULT FROM IMPROPER LOCATION OF THE PRESSURE RELIEF VALVE.

I don't mean to be an alarmist, but this warning applies to any boiler or domestic hot water heater as well, and solar energy can hurt you if you are not thinking.

The Plumbing Mechanical Package is the place where most of the potential problems with solar heating systems can be avoided. If you make your own PMP please consider the following. Leaks are not compatible with long lasting trouble free performance. A solar collector is not going to leak in its lifetime because it will be carefully braised and pressure tested. A straight piece of tubing is not likely to leak. A carefully made soldered fitting is not going to leak. If you make your own PMP with care, it will never leak either. Here is how.

Threaded fittings are much more prone to leak than a properly soldered fitting. An antifreeze solution is much thinner (less viscous) than water and is much more prone to leak. When you make a threaded fitting, screw the fittings together several times. This will tend to machine the parts together and eliminate any burrs. Use a good pipe dope and or Teflon tape.

Pressure test at 80-100 psi for 48 hours. There must be no loss of pressure at all. A solar PMP made by the Radiantec Company will be made by a senior craftsman who has made thousands. Nevertheless, a reasonably competent handyman can be successful if he selects his material with care and pays strict attention to workmanship.

Small variations in pressure (2 or 3 psi) are to be expected and are most likely due to daily temperature changes in the HTF, but other changes in pressure may indicate a problem.

If the pressure goes very high when the sun is out, the system may be flowing too slowly or not at all. Collector temperatures that are too high is confirmation.

If the system loses a little pressure every day, you probably have a leak somewhere.

If the system drops a few pounds but stabilizes at a lower pressure, the air eliminator has probably removed an air bubble.

If the system pressure falls to zero at night, but runs high during the day, the system has either lost HTF, or the expansion tank has failed, or both.

IF THE HEATING SYSTEM PRESSURE IS THE SAME AS THE BUILDING'S WATER PRESSURE, SUSPECT A BREACH IN THE WALL OF THE DOMESTIC HOT WATER HEAT EXCHANGER. ALSO SUSPECT CONTAMINATION OF THE POTABLE HOT WATER. DO NOT DRINK IT OR OTHERWISE USE IT UNTIL YOU ARE SURE THAT IT IS SAFE. THE PRESSURE RELEIF VALVE SHOULD BE SET LOWER THAN THE BUILDING'S WATER PRESSURE SO THAT THIS CONTAMINATION CANNOT OCCUR.

The pump needs to be carefully chosen for a) high quality material, and b) compatibility of the metals with the other metals in the system, and c) the ability of the pump to lift a column of HTF to the high point in the system (called pump head), and d) the ability of the pump to make the HTF flow at the proper rate, and e) the ability of the pump to do its work efficiently and with a minimum of electrical consumption.

Readers who have some familiarity with conventional heating systems know that boilers that are supplied today usually come with a pump, typically a small cheap one. I do not see how a pump can be selected without knowing anything about what kind of system the pump is going into or what the pump is going to have to do. This kind of sloppiness should not have become standard in the design of conventional heating systems, but there is no hope of a solar heating system working properly unless careful selection is paid to the pump.

If there is one thing to leave to a expert, pump selection might be it, but with the following material and the pump calculation procedures in the appendix, it can be done well. With the following information, the customer can at least verify that all important factors have been considered.

The pump is the only moving part in a Radiantec type solar heating system and this is not the place to pinch a penney. It is a reasonable goal to have a solar heating system to work flawlessly for 20 years or more. Then, replace the pump and the HTF, and have it work flawlessly for another 20 years or more. This is less maintenance than any heating system that I know of.

All moving parts should be stainless steel, but the shaft can be ceramic. If possible, the housing should be either bronze or stainless steel.

It is desirable, but not absolutely necessary, if the pump can lift a column of HTF to the high point in the system all by itself without help. When the system is properly full of fluid, the pump doesn't really have to do this. There is an equal column of HTF pulling downward to match the column of fluid going up, and the pump only has to circulate the fluid.

But if the system develops a large air bubble, or if it is trapped by steam, a smaller pump will not be able to move the fluid and a maintenance call will be needed to flush the system (but a steam trap will resolve itself when the sun goes down).

If the pump is big enough, however, all the homeowner need to do is add a little water with a garden hose, a procedure that takes ten minutes and requires no tools.

I should mention here that with reasonable workmanship and appropriate design, these problems will not happen in the first place.

A solar system should flow at the proper rate for best performance. There is some latitude here and flow does not have to be perfect for good operation, but proper flow can easily make a difference of 15-20% improvement in system energy harvest, and many owners of a solar heating system would never know the difference.

So that you will know the difference, here are the issues.

There are two types of flow. One is laminar flow, where the flow is fairly slow and smooth. Because of friction of the tubing wall, most of the flow goes through the center of the tube and the fluid nearest the wall does not circulate as well as it might. The other type of flow is turbulent flow, where the fluid sloshes around more because of its increased velocity.

Turbulent flow is good for heat exchange between the tubing and the HTF. Laminar flow is efficient as far as pump work is concerned.

What we want, is for the solar collectors and any heat exchangers to be in slightly turbulent flow. Too much turbulence wastes pump energy and in extreme cases can wear away the tubing material prematurely (erosion corrosion).

The tubing that connects the solar panels to the heat exchanger might as well be in laminar flow in order to save energy and achieve maximum service life. Use ¾" tubing up to 8 gallons per minute. Use 1" tubing up to 16 gallons per minute. Use 1 ¼" tubing up to 26 gallons per minute.

In general, a 4' X 8' solar collector should flow at the rate of 1-1 ½ gallons per minute. The temperature of the HTF coming out of the collector will be 10-15 degrees warmer than it went in under strong sunlight conditions.

This shut off valve can be used to isolate nearly all mechanical components between two valves for easier maintenance. It can also be used to adjust (meter) the flow.

This is the last line of defense against damage to the heating system from excessive pressure. The first line of defense is good design and the expansion tank. The pressure relief valve will vent the system to the atmosphere whenever a set pressure is exceeded. This valve should be set above any normal pressure situation that may occur, including stagnation. This is an emergency valve that is not designed to operate frequently. If it operates frequently because of some design flaw in the system, it will eventually start to leak and will need replacement. However, this valve should be tested once in a while to be sure that it still works and is not compromised by corrosion.

If this valve discharges, it could be quite hot, and it should be plumbed so that it will discharge in a safe place.

THIS VALVE MUST NEVER BE ISOLATED FROM THE HEAT PRODUCING EQUIPMENT (THE SOLAR COLLECTORS). THERE MUST BE NO SHUT OFF VALVE OR COMBINATION OF SHUT OFF VALVES THAT WOULD ISOLATE THE COLLECTORS FROM THE PRESSURE RELIEF VALVE.

SERIOUS MECHANICAL DAMAGE AND POTENTIAL FOR SERIOUS PERSONAL INJURY OR DEATH CAN RESULT FROM IMPROPER LOCATION OF THE PRESSURE RELIEF VALVE.

I don't mean to be an alarmist, but this warning applies to any boiler or domestic hot water heater as well, and you can get hurt by solar energy if you are not thinking.

The Plumbing Mechanical Package is the place where most of the potential problems with solar heating systems can be avoided. If you make your own PMP please consider the following. Leaks are not compatible with long lasting trouble free performance. A solar collector is not going to leak in its lifetime because it will be carefully braised and pressure tested. A straight piece of tubing is not likely to leak. A carefully made soldered fitting is not going to leak. If you make your own PMP with care, it will never leak either. Here is how.

Threaded fittings are much more prone to leak than a properly soldered fitting. An antifreeze solution is much thinner (less viscous) than water and is much more prone to leak. When you make a threaded fitting, screw the fittings together several times. This will tend to machine the parts together and eliminate any burrs. Use a good pipe dope and or Teflon tape.

Pressure test at 80-100 psi for 48 hours. There must be no loss of pressure at all. A solar PMP made by the Radiantec Company will be made by a senior craftsman who has made thousands. Nevertheless, a reasonably competent handyman can be successful if he selects his material with care and pays strict attention to workmanship.


An external DHW heat exchanger from Radiantec Company will be stainless steel and will be of the multiple plate type where solar HTF flows on one side and potable domestic hot water will flow on the other. Solar heat is transferred across the stainless steel plate without mixing of the solar HTF and the domestic hot water.

This heat exchanger is the strongest and longest lasting component of the system because failure of this part might contaminate the potable water. Accordingly, we can expect it to outlast the system in general, and thus be discarded before it ever fails. If over pressure damages the system, something else will be damaged.

DHW heat exchangers are subject to the accumulation of lime and other minerals on the potable side, which will lower the exchanger's performance and possible plug it up. Accordingly, we oversize it somewhat in order to provide a longer interval between maintenance.

Water can hold more minerals in solution when it is cold than when it is warm. When water is raised in temperature above about 140°F, the minerals will precipitate upon the heat exchanger. On the other hand, when temperatures are low, these minerals will dissolve back into the water. Solar heating systems are benefited by the fact that they often run at lower temperatures and many systems have no mineral problems at all, but some problems could be encountered in areas where there is very hard water.

However, if HX efficiency decreases significantly, you can dissolve the minerals with an acid solution, (available at plumbing supply stores). Work with acid at low temperatures and with the solar system off. Wear rubber gloves and eye protection. Do not work with an unnecessarily strong acid. Strong acids and high temperatures are dangerous. The chemical action of acid upon minerals will make heat, perhaps lots of it.

Do not wait until the system is nearly plugged up or you will have much more difficulty.

These heat exchangers are for the purpose of heating the building. Radiantec Company uses the same materials that it provides for underfloor radiant heat with the exception that extra attention is paid to high efficiency. If the energy source is oil or gas, limitations in the effectiveness of the heat exchanger can be made up for by raising the fluid temperatures.

But high operating temperatures have a very negative effect on solar collector efficiency, so we specify a highly effective radiant heating tube and we use lots of it. If we want the floor within a building to be 75°F, it would be a reasonable goal to hope the solar collectors would operate at 80-85°F.

Radiantec performed extensive research into the performance of heat exchanger materials and formed the opinion that polyethylene is superior to other materials because it is exceptionally long lasting, resistant to corrosion, has adequate temperature and pressure ratings, has smooth walls, which reduce pump work, and is reasonable in cost.

Some may wonder why we do not use a material that is more conductive such as copper. Copper is indeed many times more conductive than polyethylene, but this apparent advantage does not work out in practice. In this heat transfer situation, there are at least three factors that must be taken as a whole. It is like a chain that is only as strong as the weakest link. The three important factors are 1) the rate at which heat is brought to the heat exchanger, 2) the rate at which heat passes through the wall of the heat exchanger to the other side and 3) the rate at which the heat is carried away from the heat exchanger and put to use where it is wanted.

We can pump as much heat to the heat exchanger as we want, but as far as getting the heat away from the heat exchanger, we have to rely on the three sisters of heat transfer; conduction, convection and radiation. This means that our heat exchanger will need to have a significantly sized surface area no matter how conductive the tubing material will be.

After considering all of this, and after careful measurements and testing and research, we are of the opinion that a 4' X 8' solar collector should have about 200 ft. of 7/8" OD poly tubing (3/4" ID) if the tubing will be placed within a slab, or earth or other conductive and massive material.

Underfloor heating tubes can be placed within wooden floor systems by running tubes down the floor joists. In this case, thermal storage and heat exchanger efficiency will be reduced, but if we use the domestic hot water heater for storage and the DHW heat exchanger for heat transfer, we can compensate for to some extent.



We invite you to explore this website and to click on "Next Step" if you would like more information.

Our solar technicians are always ready to answer questions.

Call 1-800-451-7593

printer friendly version

blank